Description:
INPUT
Voltage Jumper selectable
95-132V ac or
190-264V ac
Frequency 50-60HZ nominal
Phase 1
OUTPUT
Voltage max 90V dc at 207V ac input
Current continuous 4A dc
Intermittent 6A for 10 secs
Resistance 15 ohms minimum
REGULATION
+/-1%
THERMAL DRIFT
0.05% per deg. C change in AVR ambient
TYPICAL SYSTEM RESPONSE
AVR respone 20ms
Filed current to 90% 80ms
Machine Volts to 97% 300ms
EXTERNAL VOLTAGE ADJUSTMENT
+/-10% with 1k ohm 1 watt trimmer
UNDER FREQUENCY PROTECTION
Set point 95%HZ
Slope 170% down to 30HZ
UNIT POWER DISSIPATION
10 watts maximum
BUILD UP VOLTAGE
4 Volts @ AVR terminals
Environmental
Vibration 20-100HZ 50mm/sec
100Hz 2kHz 3.3g
Operating temperature -40 to +70 C
Relative Humidity 0-70C 95%
Storage temperature -55 to +80 C
Notes:
1. With 4% engune governing
2. After 10 minutes.
3. Applies to Mod status F onwards. Generator de-rate may apply. Check with factory.
4. Factor set, semi-sealed, jumper selectable.
5. Non condensing.